EI 96 - Transformer TM 88



General characteristics

Primary tension  (V) : 230/40015 Reference standards: EN61558-UL506 
Frequency  (Hz) : 50-60  Certificates of the product: UL 
Ambient temperature  (C): 40  Winding:  
Thermic insulation class: F  Treatment:  
High voltage  (V) : 4500  Protection type:  
Electric insulation class: I  Fixing: Snap mounting bar 50022-35mm 
Service: Continuos  Earth connection:  
Protection index: IP00  Frequency deviation: 10%  

Type:89TM for pri 2x115;90TM for pri 230V; 91TM 2305%; 92TM 400V; 93TM 4005%; 43TM 230-400


Power(VA): 160,00
Code Secondary tension (V) Power(VA)
cos φ=0,5
No-load voltage Δ (%) Efficiency (%) Weight (Kg) H (mm) A (mm) B (mm) E (mm)
88TM160C 12 385 8 86 2,8 121 96 80 105
88TM160F 24 385 8 86 2,8 121 96 80 105
88TM1602 230 385 8 86 2,8 121 96 80 105
88TM1607 42 385 8 86 2,8 121 96 80 105
88TM160W 48 385 8 86 2,8 121 96 80 105
88TM160V 115 385 8 86 2,8 121 96 80 105
 
Power(VA): 200,00
Code Secondary tension (V) Power(VA)
cos φ=0,5
No-load voltage Δ (%) Efficiency (%) Weight (Kg) H (mm) A (mm) B (mm) E (mm)
88TM200C 12 410 8 89 3,5 121 96 80 118
88TM200F 24 410 8 89 3,5 121 96 80 118
88TM2002 230 410 8 89 3,5 121 96 80 118
88TM2007 42 410 8 89 3,5 121 96 80 118
88TM200W 48 410 8 89 3,5 121 96 80 118
88TM200V 115 410 8 89 3,5 121 96 80 118

Power(VA): 250,00
Code Secondary tension (V) Power(VA)
cos φ=0,5
No-load voltage Δ (%) Efficiency (%) Weight (Kg) H (mm) A (mm) B (mm) E (mm)
88TM250C 12 585 7 89 3,6 121 96 80 118
88TM250F 24 585 7 89 3,6 121 96 80 118
88TM2502 230 585 7 89 3,6 121 96 80 118
88TM2507 42 585 7 89 3,6 121 96 80 118
88TM250W 48 585 7 89 3,6 121 96 80 118
88TM250V 115 585 7 89 3,6 121 96 80 118